The Saturn Geo X Norma Earth Ground Tester is a professional earth resistance meter made under the LEM NORMA name, a range later continued by Fluke. This used Norma Earth Ground Tester measures ground electrodes, earthing systems and low resistances for electrical installers, utilities, telecom sites and lightning protection contractors.
Norma Earth Ground Tester Overview
The rotary switch on this Saturn Geo X gives three groups of tests. Ground resistance (RA) can be measured with the classic 3-pole and 4-pole fall-of-potential methods, and with selective 3-pole and 4-pole measurement using a current clamp, so one electrode can be checked without disconnecting it from a meshed earthing system.

The R~ position measures 2-pole AC resistance, and the low resistance position measures 2-pole and 4-pole DC resistance for bonding and continuity checks. The display also shows the interference voltage (U) on the test leads before a measurement starts.
Key Features
- 3-pole and 4-pole earth resistance measurement
- Selective 3-pole and 4-pole earth measurement with a current clamp input
- 2-pole AC resistance measurement
- 2-pole and 4-pole low resistance measurement
- Interference voltage display before testing
- Large LCD with START, DISPLAY, CHANGE and SELECT keys
- Rubber protective holster
Technical Specifications
| Specification | Detail |
| Model | SATURN GEO X (LEM NORMA Earth / Ground Tester) |
| Ground resistance (RA) | 3-pole, 4-pole, selective 3-pole / 4-pole with clamp; range up to 300 kΩ (dial marking) |
| AC resistance (R~) | 2-pole, up to 300 kΩ (dial marking) |
| Low resistance (R DC) | 2-pole and 4-pole, up to 3 kΩ (dial marking) |
| Test voltage | 48 V AC (shown on display; Saturn Geo family specification) |
| Measuring frequency | 128 Hz (Saturn Geo family specification) |
| Terminals | C2 (H), P2 (S), clamp input, P1 (ES), C1 (E) |
| Condition | Used |
Norma Earth Ground Tester Test Methods Compared
| Method | Stakes | Best for |
| 3-pole fall of potential | 2 auxiliary stakes | Quick checks of a single electrode |
| 4-pole fall of potential | 2 auxiliary stakes | Low-value earths, cancels lead resistance |
| Selective (with clamp) | 2 auxiliary stakes + clamp | One electrode in a connected system, no disconnection |
| 2-pole | 1 known reference earth | Where stakes cannot be driven |
Applications
- Testing new and existing earth electrodes on switchboards and substations
- Lightning protection system verification
- Telecom tower and communications site earthing
- Bonding and continuity checks with the low resistance function
What You Receive
You receive the tester only, as shown. Test leads, stakes, the current clamp, manuals and software are not included. Because it is a used unit, check calibration before relying on results for compliance testing.
Frequently Asked Questions
Is the Saturn Geo X the same as a Fluke tester?
The Saturn Geo range was sold under the LEM NORMA name. Fluke later took over this earth tester line, which is why it is often listed with Fluke.
Does it need a clamp for selective testing?
Yes. Selective measurement needs a compatible current clamp connected to the clamp input. A clamp is not included with this item.
Sources: LEM Saturn Geo plus technical data, TEquipment Saturn GEO X, Fluke 1625 earth tester manual